Cooper Connection Search Cooper Industries Cooper Industries Home Cooper

What's NewCooper B-Line

B-Line Introduces 400 Amp Self-Contained Meter-Main With Provision for Additional Main Breaker
Features
  • 200 Amp, 8-circuit feed-thru load-center with 200 amp amp breaker
  • Provision for additional main breaker (125-200 amp)
  • Manual circuit closing bypass on MCC style

Standards

  • UL 67 listed
  • Complies with ANSI C12.7

Construction

  • 38" high x 30" wide x 6" deep
  • Ring style
  • Type 3R
  • Underground feed
  • Surface mount
  • Load Side hinged padlockable door

Finish

  • ANSI 61 gray acrylic electrocoat finish

Accessories

  • Line lug kit - catalog #50881A
  • Overhead feed conversion kit - catalog #CK8326
  • Breaker filler plate - catalog #25319
  • Flush trim kit - catalog #FK3038

Catalog
Number
Main
Disconnect
Provision Branch
Circuits
A/C Rating Ampacity Voltage Service
Type
No.
of
Jaws
Bypass
U4042208MC (1) 200A 2P CB (1) 2P CB (125-200A) 8/16 22K 400 Max 120/240 1-Phase 3-Wire 4 None
U4042208MCC MCC

Note: Main breaker provision accepts Siemens Circuit breaker Type "QPP" for 10K AIC or "QPHH" for 22K AIC rating.

Download PDF version of Product Sheet

 

For more information on Cooper B-Line's products, visit our online product information, contact your local Cooper B-Line representative, or contact us through our feedback / inquiry form.

Home | About Us | What's New | Products | Library | Design Center |
Services | Employment | Contact UsSearch

 

 


Copyright © 2008 Cooper B-Line®, Inc.  All rights reserved.  Legal Notices
Questions?  Please email webmaster@CooperIndustries.com
618.654.2184  |  509 W. Monroe St.  Highland, IL 62249  | Customer Service